Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C15-1346
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

T.I.: REMODEL FOR RESTAURANT. NEW FINISHES AND EQUIPMENT - TC

CONTRACTOR TO PAY INSPECTION FEES BEFORE PERMIT CAN BE ISSUED

Status: Closed
Project Name: ROUND TABLE PIZZA
Review Type: Plumbing
Result: Correction
Result Date: 4/29/2015 12:53:00 PM

Comments:

 Code SectionReview CommentStatus
1_

Reviewed by: Bergstrom, Leigh W.                                         Permit #: C15-1458

Phone: 343-8326                                                                         Date: 4/29/2015

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tommy Cornell

Phone: 343-8181

Email: CornellTA@muni.org

Project: Round Table Pizza

Review Number: 350773

 

STATUS:   4-29-15 Comments to be addressed.

The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.

 



2_
M2.1        The cast iron or copper DWV waste piping and branch fitting that serve FS-1 at the soda dispenser are not compatible with the disposed byproducts. (UPC 313.4)

3_

M2.1     The 3-compartment sink requires a center waste outlet (UPC 1001.2) with separate vented P-trap (UPC 1014.1.1).



4_
1, 2 & 4/M2.2      The 3/4" gas branch serving WH-1 (125 MBH @ 100 feet)and the 1" gas main serving the oven and WH-1 (260 MBH @ 100 feet) appear to be undersized per UPC Table 12-8.

5_
2/M2.2     Provide the flow setting required to keep the HWC velocity below 5 FPS. (UPC 610.12.1)

6_
2/M3.2         Is it intended to insulate the rooftop gas piping? Please clarify.




Advisory Information:

When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature.                                                 

RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter