Permit Number: C15-1284
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

TENANT IMPROVEMENT - TC 

SHELL AND STORE FRONT C15-1149

CONTRACTOR TO PAY FOR INSPECTION FEES

Status: Closed
Project Name: ULTA BEAUTY
Review Type: Fire
Result: Correction
Result Date: 4/27/2015 11:02:09 AM

Comments:

 Code SectionReview CommentStatus
1_
Show size, type, & location of fire extinguishers (FE's) as required per IFC 906 to include one on the mezzanine.  FE's shall be located along the path of egress at or near exit doors.  Provide either a mounting detail or note to insure height requirements are met.  The note on sheet CS1 referencing to coordinate exact locations with the fire marshall needs to be done as part of the plan review process.  field adjustments may occurr providing compliance with IFC 906 is maintained.