AIR HANDELING UNIT
Reference the RAH-ED1 design and details. Whatever is being used for construction needs to be stamped and signed by an engineer licensed in Alaska. Based on what has been provided it is recommended that page1 and the details at the end be stamped and signed. It may be possible to only stamp page 1 as well as it appears all necessary information is on this sheet. Reference the Alaska State Statutes section 08.48.221.
AIR CURTAIN SUPPORT DESIGN
Reference the design of the air curtain support. Air curtains generally generate their own force when active. Please verify that this force is less than the design seismic force. Reference IBC section 1604.4.