Permit Number: C15-1104
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location:
Work Description:

Unit# D20A - Comm T/I to include plumb/mech/electric - BWP

 

**Contractor to pay for inspections and any additional charges**

Status: Closed
Project Name: Lululemon Athletica
Review Type: Fire
Result: Approved
Result Date: 4/2/2015 11:24:46 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Page G003 Code Study: Correct code study to actually reflect existing building.  This bldg is not 1 story nor is it V-N construction.

2_Resolved

Provide hardware detail on doors 01 and 01A, for sliding doors and security grill.  Provide locking details.  Thumb turn locks are prohibited.   "doors to remain unlocked while space is occupied" is required over locking doors.



Note:  sliding bolts are not acceptable.  I will approve the permit, but an approved method of locking the grill gate will have to be installed.  Single motion, no effort, no special knowledge required. 

3_Resolved
Mall is in process of installing voice evac system, this space shall have compatable devices installed with new system for Mall. 