Permit Number: C15-1220
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

NEW KITCHEN EQUIPMENT, DINING REMODEL AND EXPANSION-GJS

REASSIGNED TO BOB PARKER-GJS

Status: Issued
Project Name: THE PERFECT CUP
Review Type: Architectural
Result: Correction
Result Date: 3/27/2015 2:57:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved

Reviewed by: Bergstrom, Leigh W.                                                 Permit #: C15-1220

Phone: 343-8326                                                                              Date: 3/27/2015

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Bob Parker 

Phone: 343-8391

Email: ParkerRW@muni.org

Project: The Perfect Cup

Review Number: 348692



2_

STATUS:   3-27-15 Comments to be addressed.

The following comments based upon the 2009 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.



3_
A1.1        This floor plan depicts about a 70% solid wall store front, while A2.1 "Demo" and A2.2 "New" depict about a 90% Glass storefront. Please clarify.

4_
A1.1        This Fire Code Diagram shows two store front exits, while A2.2 "New" shows only one. Please clarify and indicate the type of door(s).

5_
A.1.         Indicate rated walls.

6_
Provide a kitchen/bar equipment plan and schedule to include equipment loads, required utility connections and sizes and indications of (N) new or (E) existing.

7_
A2.1        There is additional demolition work in the kitchen area that is not indicated.

8_
A2.2        Clarify location of new walls with details of construction and wall heights.

9_
Provide a door schedule to include but not limited to hardware, (E) or (N) and fire rating.

10_
A2.2        Provide room or area indicators of use such as stairs, storage, office, hallway, electric, Etc.

11_
A2.2        Clarify what 3070 means on the doors that are so marked.

12_
A2.2        The new hood and new stove as marked are actually existing according to the mechanical drawings and sheet A2.1.




Advisory Information:

 

When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature.

RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.

 