Permit Number: C15-1161
Permit Type: Commercial Building Permit - None BldgNew
Address: 1612 ANCHORAGE PORT RD Anchorage
Location:
Work Description:

3,150 sq ft comm bldg and bulk fuel tank / tb **Master file tank farm & controls bldg**

C15-1215 780 sq ft new truck loading/fuel station bldg; C15-1216 Bulk fuel tank & retaining wall

MOA & FIRE - 1/2 size; FIELD full size

Status: Expired
Project Name: POA BULK TERMINAL DELTA WESTERN
Review Type: Fire
Result: Correction
Result Date: 4/30/2015 11:29:45 AM

Comments:

 Code SectionReview CommentStatus
1_
Sht. SG-01 - Clarification needed on if there a specific commodity to be stored in the warm storage building.  Please identify commodity. 

2_
SG-01- Clarification needed for Exterior lock set A to be applied to exit door.

3_
Sht. SG04- Address not indicated on building of elevation page.  Provide building identification; numerals must be contrasting and large enough to be visible from roadway for first responders.  IFC 505.1

4_
Sht. SG-04 - Knox Box required on building for fire dept. access.  Revise plans to show knox box on front of building; to be mounted no higher than 6 ft at main entrance.  Contact AFD 267-4901 to schedule with captain on duty to have keys to main entrance and all control areas / knox cap installed once box is mounted.  IFC 506.1

5_
No code study was provided for the methanol storage tank/loading station.  Please provide a full code study and architectural drawings stamped and signed by an arcitect licensed in Alaska as required by Alaska State Statute Sec. 08.48.221.  Ref. AMC Sec.  23.10.104.8.  A full review has not been provided.

6_

Provide civil drawings showing fire dept. access at all points to building and tank.  Hydrant must be available and accessible within 600 ft to all exterior.  Show/indicate width of gate on plans.  IFC 507.5.1/ Appendix C & D.  A full plan review has not been provided.

 