Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C15-1161
Permit Type: Commercial Building Permit - None BldgNew
Address: 1612 ANCHORAGE PORT RD Anchorage
Location:
Work Description:

3,150 sq ft comm bldg and bulk fuel tank / tb **Master file tank farm & controls bldg**

C15-1215 780 sq ft new truck loading/fuel station bldg; C15-1216 Bulk fuel tank & retaining wall

MOA & FIRE - 1/2 size; FIELD full size

Status: Expired
Project Name: POA BULK TERMINAL DELTA WESTERN
Review Type: Architectural
Result: Correction
Result Date: 4/10/2015 1:15:50 PM

Comments:

 Code SectionReview CommentStatus
1_

ARCHITECTURAL DRAWINGS

Please provide a code study and Architectural Drawings that are stamped and signed by an architect licensed in Alaska as required by the Alaska State Statutes section 08.48.221. Reference AMC section 23.10.104.8. A full architectural review has not been provided.



2_

CONSTRUCTION TYPE

Reference sheets SG-01 and SG-05 of the drawings. The type of construction has been indicated as type IIB, and yet there are wood walls shown on sheet SG-05. Combustible material is permitted in Type IIB construction in limited conditions. This does not appear to be one of the conditions in which it is permitted. Reference IBC section 603.1.






Advisory Information:

Reviewed by: Bolen, Wayne A.                                                  Permit #: C15-1127

Phone: 343-8072                                                                       Date: 4/10/2015

Fax: 249-7393

Email: BolenWA@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: MOA Bulk Terminal Tank and Control Building

Review Number: 348023

____________________________________________________________________________________

 

PERMIT STATUS

4/10/2015 – Review incomplete. Comments issued. A full architectural review will be provided once a revised code study and drawings that are stamped and signed by an architect in Alaska are submitted.

 

Advisory Comment (no response required):  This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.

 

Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revise drawings.

 

All submittals should be sent to the permit manager.

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS