Permit Number: F15-1083
Permit Type: Commercial Trade Permit - New Fire
Address: 1700 HILLCREST DR Anchorage
Location:
Work Description: 27,000 sq ft add'n & renovation in support of career technology classrooms @ West High School / tb
Status: Closed
Project Name: Child Permit of C14-1704
Review Type: Fire System
Result: Approved
Result Date: 4/9/2015 9:20:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Municipality of Anchorage

 

Building Safety Division

 

Fire System Comments

 

Reviewed by: Mark Warren                                                         Permit #: F15-1083

Phone: 343-8072                                                                        Date: 3/20/2015, approved 4/10/2015

Fax: 249-7393

Email: warrenmj@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: West High addition               

Review Number: 347693

____________________________________________________________________________________

 

PERMIT STATUS: Corrections

 

1)       It looks like a new elevator. There is a heat detector In the elevator machine room that initiates a shunt and be placed next to a sprinkler head. Provide information on the elevator as to what type if it is a gen II.

2)       The horn strobe at the east end of the corridor 101 to be line of site of the horn strobe on the west end.

3)       Clarify cat walk at second floor as to location and annunciation required.

4)       What is the bell on page FA-03, is it an existing bell and what purpose does it have?

The items above are approved with a new set of plans. 4/10/2015.

 