Permit Number: C15-1015
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

Comm T/I to include plumb/mech/electric - Contractor to pay for Inspections - Charge additional expedited fees if over 60 inspections to MBH Architects -  BWP

 

**DO NOT ISSUE UNTIL C14-1563 HAS A CO OR CCO**   

Status: Closed
Project Name: H & M RETAIL
Review Type: Structural
Result: Approved
Result Date: 3/7/2015 9:35:32 AM

Comments:

 Code SectionReview CommentStatus
1AMC 23.15.1704.1.4Local amendment:
Unless otherwise approved by the building official, special inspectors shall be pre-qualified and approved by the building official before performing special inspection activities on any project within the Municipality. Special inspectors shall obtain pre-approval for each category of inspection they wish to perform.
Resolved
Please provide a letter from the Owner or Special Inspection Agency stating that the Owner has retained the Agency to provide required special inspection services.

2_Resolved
PARTITION SUPPORT AT INTERIOR SOFFIT
Refer to Sheet S-110, Details 1/S-212, 3/S-222. Please clarify how the partition at the second-level entry is braced against lateral displacement with the interference of the soffit shown per Detail 1/S-212. No calculations were provided that address this condition.