Permit Number: C15-1015
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

Comm T/I to include plumb/mech/electric - Contractor to pay for Inspections - Charge additional expedited fees if over 60 inspections to MBH Architects -  BWP

 

**DO NOT ISSUE UNTIL C14-1563 HAS A CO OR CCO**   

Status: Closed
Project Name: H & M RETAIL
Review Type: Fire
Result: Approved
Result Date: 2/23/2015 4:57:44 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Pg A-000.00-code Analysis, Construction Ratings.  Correct rates for columns, bearing walls interior, non-bearing walls, beams, trussess, roof/ceiling, etc.  Plans show NON-RATED, actual rating per Table 601 s/b 3 hrs.



2_Resolved
 Pg A-000.00-Occupant load calcs reference 2958 s.f. of unoccupied area.,  Show on plans; where those areas are and explain what use/occupancy they are for. 



3_Resolved
Pg. A-800.00 Door note 4-Sign on exit doors shall say "This door to remain unlocked while space is occupied.  IBC 1008.1.9.3.2.2.  Please change sign and code reference.

 

4. Doors 1 and 13, change sign per comment 3.

 

5.   It appears there are several rooms that have elect. locked egress doors.  In addition to meeting IBC 1008.1.9.8, they must automatically unlock on power loss, alarm and fire flow. 

 

 





4_Resolved
Doors 1 and 13, change sign per comment 3.



5_Resolved
It appears there are several rooms that have elect. locked egress doors.  In addition to meeting IBC 1008.1.9.8, they must automatically unlock on power loss, alarm and fire flow. 