Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C15-1104
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location:
Work Description:

Unit# D20A - Comm T/I to include plumb/mech/electric - BWP

 

**Contractor to pay for inspections and any additional charges**

Status: Closed
Project Name: Lululemon Athletica
Review Type: Architectural
Result: Correction
Result Date: 3/2/2015 3:10:00 PM

Comments:

 Code SectionReview CommentStatus
1_

STATUS:   3-02-15 Comments to be addressed.

The following comments based upon the 2009 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.



2_
G003 Building Code Summary         The existing building is 4 stories (not 1) and Type I-B construction (not V-N). Please adjust the code study.

3_
A120          Provide clarification to keynote #4 (HVAC) pointing to the oval soffit.

4_
Provide structural and seismic calculations plus fastening details for the soffit ceiling (A121) and the overhead coiling security grilles 01 & 01A (1/A714) to include engineers stamp and signature on a deferred submittal basis.

5_
3/A212         The 2'-10" dimension to the countertop is a maximum dimension to the flood rim of the sink per ICC/ANSI A117.1-606.3. Please clarify.

6_
A310         The maximum allowable dimension AFF for the horizontal grab bars at an ADA water closet is 36" to the top of the gripping surface per ICC/ANSI A117.1-609.4. 

7_
A310            The maximum allowable ADA mirror mounting height is 40 " AFF to the bottom of the reflecting surface per ICC/ANSI A117.1-603.3. Please clarify.

8_
A610           The back corridor is rated for 1-Hour requiring door #7 to be rated for 45 minutes per IBC Table 715.4. Provide clarification.




Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                                 Permit #: C15-1104

Phone: 343-8326                                                                              Date: 3/02/2015

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Bob Parker 

Phone: 343-8391

Email: ParkerRW@muni.org

Project: Lululemon Athletics

Review Number: 347047

 

When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature.

RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.

 

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS