Comm T/I to include plumb/mech/electric - Contractor to pay for Inspections - Charge additional expedited fees if over 60 inspections to MBH Architects - BWP
**DO NOT ISSUE UNTIL C14-1563 HAS A CO OR CCO**
Reviewed by: Bergstrom, Leigh W. Permit #: C15-1015
Phone: 343-8326 Date: 1/14/2015
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Bob Parker
Phone: 343-8391
Email: ParkerRW@muni.org
Project: H & M Retail
Review Number: 345611
1) STATUS: 1-14-15 Comments to be addressed.
2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.
3) P-220 The existing rainleader system, existing rooftop units and existing gas piping all appear to be double printed (side by side).
4) 1/P-310 Clarify note #11.
5) 1 & 2/P-310 On the core and shell permit drawings sheet M2.02, the elevator sump pump piping is shown to run to a downspout nozzle on the exterior of the building. On the tenant improvement drawings it runs to a floor sink on the second floor. Please clarify.
6) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.