Permit Number: C15-1015
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

Comm T/I to include plumb/mech/electric - Contractor to pay for Inspections - Charge additional expedited fees if over 60 inspections to MBH Architects -  BWP

 

**DO NOT ISSUE UNTIL C14-1563 HAS A CO OR CCO**   

Status: Closed
Project Name: H & M RETAIL
Review Type: Electrical
Result: Correction
Result Date: 1/15/2015 10:15:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Electrical Comments

 

Reviewed by: David Abuobaid                                                   Permit #: C15-1015

Phone: 343-8333                                                                        Date: 1/15/2015

Fax:     249-7775

Email:  AbuobaidDH@muni.org

Permit  Manager: Tony Barganier

Phone: 343-8339

Email:  BarganierWA@muni.org

Project: H & M (Fax: no fax provided)

____________________________________________________________________________________

1. The following comments based on the 2011 National Electrical Code (NEC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the NEC or any federal, state or local regulations.

 

2.  TRANSFORMER (T1) FIRE RATED HOUSING:

Sheet E-030 (Line Diagram – 225 KVA Transformer Fire Rating Housing). NEC Section 450.21(B) requires transformer larger than 112.5KVA to be installed in a fire resistant room of minimum 1-hr fire rating. Please address.                                                                                                                                                                                                                                                                                                                                                                                                               

 

3  TRANSFORMER MOUNTING (STRUCTURAL REVIEW)

Sheet E-030 (One Line Diagram – Transformer). Provide structural, seismic and wind load calculations as applicable, plus fastening details for the transformer to include engineers stamp and signature, for structural review on a deferred submittal basis. Refer to Anchorage Administrative Code AAC 23.10.104.8.1. Please address.

 

4.  When the above comments have been addressed, please update the electrical plans at the MOA Plans Review Office with three (3) sets of revised electrical pages to include clouded changes, electrical engineers stamp and signature.   

 