Fire Plan Review
Initial Review 9/5/14, 2nd review 10/21)
3rd review 12/15/14 All comments addressed and resolved. Plans Approved.
Review Status: F&F approved, Architectural has Comments
Comments:
1. F&F approved 9/5/14...12/2/14 Core ;& Shell approved
1. Mechanical Room C260 over 500 s.f. needs 2nd exit IF heating equipment is 400,000 or greater. Provide BTU rating of equipment or verify it's less than 400,000. (10/13-resolved, no heating equip. in this room).
2. Submit architectural, and all the rest (resolved and submitted)
3. What is the cat walk for in C154? What will it be used for?
4. WA303-What is the duct along side of the cat wak ladder?
5. A602-provide flame spread specs for fabric panels, and provide locations of where they will be.
6. What type of activities are done in the applied learning lab, mini-lab C154-D C152A and lab C152?
7. WM003 & 004-AHU's 2000 c.f.m or greater require smoke detection shut off.
8. WE201-LabC152 requires emergency lights.