Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C14-1704
Permit Type: Commercial Building Permit - None BldgCombo
Address: 1700 HILLCREST DR Anchorage
Location:
Work Description: 27,000 sq ft add'n & renovation in support of career technology classrooms @ West High School / tb
Status: Closed
Project Name: WEST HIGH SCHOOL
Review Type: Fire
Result: Approved
Result Date: 12/15/2014 9:24:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Fire Plan Review

 

Initial Review 9/5/14, 2nd review 10/21)

3rd review 12/15/14 All comments addressed and resolved.  Plans Approved.   

Review Status:  F&F approved, Architectural has Comments

 

Comments:

 

1.  F&F approved 9/5/14...12/2/14 Core ;& Shell approved

 

1.  Mechanical Room C260 over 500 s.f. needs 2nd exit IF heating equipment is 400,000 or greater.  Provide BTU rating of equipment  or verify it's less than 400,000.  (10/13-resolved, no heating equip. in this room).

 

2.  Submit architectural, and all the rest (resolved and submitted)

 

3.  What is the cat walk for in C154?  What will it be used for?

 

4.  WA303-What is the duct along side of the cat wak ladder?

 

5.  A602-provide flame spread specs for fabric panels, and provide locations of where they will be.

 

6.  What type of activities are done in the applied learning lab, mini-lab C154-D C152A and lab C152?

 

7.  WM003 & 004-AHU's 2000 c.f.m or greater require smoke detection shut off. 

 

8.  WE201-LabC152 requires emergency lights.

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS