Permit Number: X14-2426
Permit Type: Commercial Building Permit - ChangeOrdr BldgCombo
Address: 1700 HILLCREST DR Anchorage
Location:
Work Description: Rivesed frame base plate details and strengthening of connections - BWP
Status: Closed
Project Name: Change Order of Bldg App C14-1704
Review Type: Structural
Result: Correction
Result Date: 12/16/2014 8:27:56 AM

Comments:

 Code SectionReview CommentStatus
1_

ANCHOR DESIGN

Reference the design of the anchors. Please clarify why the anchors are not designed to the expected capacity of the braces as required by AISC 341-05 section 8.5a. Please design anchors to strength level forces as required by IBC section 1912.



2_

END PLATE DESIGN

Please provide design of the plates at the end of the anchor bolt groups for the new loads. Since the bearing stress have been changed on the plate both bearing on the concrete and the plate size must be verified. Reference AISC 360-05 sections J8 and F11, and ACI 318-08 section 10.14.






Advisory Information:

Reviewed by: Bolen, Wayne A.                                                  Permit #: C14-1704

Phone: 343-8072                                                                        Date: 12/16/2014

Fax: 249-7393

Email: BolenWA@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: West Romig Braced Frame Anchor Misplacement Fix

Review Number: 344681

____________________________________________________________________________________

 

PERMIT STATUS

12/16/2014 – Review complete. Comments issued.

 

Advisory Comment (no response required):  This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.

 

Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revise drawings.

 

All submittals should be sent to the permit manager.

 