Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C14-1805
Permit Type: Commercial Building Permit - None BldgAlter
Address: 2801 DEBARR RD Anchorage
Location:
Work Description:

Comm T/I: renovation of the Emergency Department; includes elec, plbg, mech / tb


Status: Closed
Project Name: ALASKA REGIONAL EMERGENCY DEPARTMENT
Review Type: Architectural
Result: Approved
Result Date: 12/15/2014 12:41:47 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Crafts, Donald E.                                                  Permit #: C14-1805

Phone: 343-8451                                                           Date: 09/30/14, 10/07/14, 11/20/14, 12/15/14

Fax: 249-7652

Email: CraftsDE@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierT@muni.org

Project: ALASKA REGIONAL EMERGENCY - 2801 DEBARR RD

Review Number: 344608

 

1.  Status: Architectural Corrections required.  10/07/14   Status: Architectural Corrections required.  10/07/14     Status: Architectural Corrections required.  11/20/14   Status: Full Architectural Approval.  12/15/14

 

2.  The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued.  The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.

 

3.  Drawing No. CVR, Plan Review Data; Revise: National Electric Code (NEC) 2008 Edition to National Electric Code (NEC) 2011 Edition.  10/07/14      RESOLVED.  11/20/14

 

Note that Special Inspection is required for all applications of sprayed fire-resistant materials in accordance with IBC Section 1704.12.  Please provide a Special Inspector for this sprayed fire-resistant material application.

 

Please resolve all fire comments and copy me on the responses.      MOSTLY RESOLVED.  See below.  11/20/14        RESOLVED.  12/15/14

 

The following Fire Comment is not resolved.:

"5.  1.02EN-explain the "lock down and release" function of doors 2E109A, 2E108, 2E109B. Are these doors able to open in the direction egress under lockdown mode?

 The questions remains. Are these doors able to open in the direction of egress under lockdown mode?  If not, then additional exiting will be required that cannot be locked down.  Or lockdown mode will have to be removed from required exits. "

 

Please provide the release function of doors 2E109A, 2E108, 2E109B that meets the requirements of IBC Section 1008.1.9.6, 1008.1.9.7, or 1008.1.9.8.   Note that IBC Section 1008.1.9.9 only applies to correctional facilities and can not be used with out an approved "Request for Alternate Design, Materials, and Methods of Construction" by both the Building Official and the Fire Marshall.  11/20/14 

 

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS