Fire Plan Review
Status: Approved by redlining plans. 12/8/14 All exiting issues addressed.
Comments:
1. From the North West corner office to the area of the FEC on the post is over 100 ft common path of egress distance. Same from the Storage room (just a little over 100 ft common path)
2. Exit door 06-exit width is not free and clear. Office walls and/or desk configuration blocking clear path of egress.
3. Users of both conference rooms and restrooms only have access to 1 exit, due to the card readers on doors 08, 05 and 03 and 10. They need free and clear access to 2 exits.
4. Exit 09 leading thru 2 conference rooms does not provide a clear and discernable path.
5. Provide exiting plan for this floor, showing all card reader devices and controlled exiting devices so we can evaluate further. Only one exit is allowed a controll device. Please provide info on the elevator lobby doors too.
Maybe a brainstorming meeting would be appropriate if you wish.