Structural Comments
Reviewed by: Wehr, Rodney E. Permit #: C14-2177
Phone: 343-7585 Date: 12/19/2014
Fax: 249-7531
Email: WehrRE@muni.org
Permit Manager: Tommy Cornell
Phone: 343-8181
Email: CornellTA@muni.org
Project: C14-2177
Review Number: 344147
____________________________________________________________________________________
PERMIT STATUS
12/19/2014 – Review complete. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
1. The structural plans are required to be signed and sealed by an engineer registered in the state of Alaska, the stamp on the plans is from Alabama. Please revise.
2. Clarify what the grill support column “by others” will be. This appears to be a structural item and as such, should be on the structural plans.
3. Provided calculations for the proposed design.
4. Provide letter from the inspector/inspection agency that will be performing the special inspection for this project.
5. (No response required) Additional comments may be made based on the responses received.
Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revise drawings. While not required it is extremely helpful to the reviewer if the response indicates where in the submittal each comments has been addressed.
All submittals should be sent to the permit manager.