Permit Number: C14-2177
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location:
Work Description: T.I.: STRUC, PLMB, MECH, ELEC. SUITE 207A - TC
Status: Closed
Project Name: BATH & BODY WORKS
Review Type: Fire
Result: Correction
Result Date: 12/19/2014 6:21:13 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Fire Plan Review

 

 

 

Comments: 

 

1.  A00.2 Hardware group A1-roll up door lists thumb turn lock on inside.  Thumbturn locks are prohibited by local policy. Is the emergency release for dropping the security grille or for raising the grille?

 

2.  Shiplap wood planking, provide spec. sheet showing finish meeting IBC 803.9.  Same finish information for cloth hangings. 

 

3.  Exit signs-additional exit signs could be required, I only see 3 on the plans, ceiling mounted, I don't believe the rear exit is visible from all corners of the store. 

 

4.  Extinguishers are mentioned in the plan notes, but not shown on the plans. 