Reviewed by: Bergstrom, Leigh W. Permit #: C14-1705
Phone: 343-8326 Date: 11/26/2014
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: Romig Middle School Addition & Renovation
Review Number: 343417
1) STATUS: 8-14-14 Approved for footing, foundation and underground only. Provide 100% drawings. Comments to be addressed. 10-20-14 COMMENTS TO BE ADDRESSED. 11-26-14 APPROVED.
2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations. RESOLVED 11-26-14.
3) Provide structural, seismic and wind load calculations as applicable, plus fastening details for R-GT-1, R-DC-1 & ROA5 to include engineers stamp and signature, for structural review on a deferred submittal basis. RESOLVED 11-26-14.
4) RM004 Provide the minimum outside air setting required for ROA5 per IMC Table 403.3. RESOLVED PER RE-SUBMITTAL RECEIVED 11-13-14.
5) 7/MR803 Dryer exhaust duct discharge outlets are required to have backdraft dampers per IMC 504.4. RESOLVED PER RE-SUBMITTAL RECEIVED 11-13-14.
6) 7/MR803 Clarify the reference to IMC 540. RESOLVED PER RE-SUBMITTAL RECEIVED 11-13-14.
7) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. RESOLVED 11-26-14.