Permit Number: C14-1704
Permit Type: Commercial Building Permit - None BldgCombo
Address: 1700 HILLCREST DR Anchorage
Location:
Work Description: 27,000 sq ft add'n & renovation in support of career technology classrooms @ West High School / tb
Status: Closed
Project Name: WEST HIGH SCHOOL
Review Type: Mechanical
Result: Approved
Result Date: 11/20/2014 11:26:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C14-1704

Phone: 343-8326                                                                           Date: 11/20/2014

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: West High School

Review Number: 343410

 

1) STATUS:   4-5-14 Comments to be addressed.         11-20-14 APPROVED.

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.      RESOLVED 11-20-14. 

 

3) Provide structural, seismic and wind load calculations as applicable, plus fastening details for W-GT-1, W-RF-1, AC-1 & W-AHU-1 & 2 to include engineers stamp and signature, for structural review on a deferred submittal basis.        RESOLVED 11-20-14.

 

4) WM401           According to the code plan on A004, the north side corridor wall is not rated and would not require fire dampers on the transfer air duct penetrations through that wall. Coordinate with the architect.         RESOLVED PER RESUBMITTAL RECEIVED 11-13-14.

 

5) WM401           If the wall mentioned in comment #4 is required to be rated, the exhaust duct penetration of that wall from W-EF-7 would also require a fire damper. (IMC 607.5.3)        RESOLVED PER RESUBMITTAL RECEIVED 11-13-14.

 

6) 4/WM804        The discription of an "AIR TRANSFER DUCT DETAIL (DOWN TURNED)" does not correspond with the HWS & HWR details.    RESOLVED PER RESUBMITTAL RECEIVED 11-13-14.

 

7) 5/WM804        Clarify the location of the clothes dryer to which this detail applies.       RESOLVED PER RESUBMITTAL RECEIVED 11-13-14.

 

8) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.                                RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.         RESOLVED 11-20-14.