Reviewed by: Mark Warren Permit #: F14-1276
Phone: 343-8072 Date: 11/18/2014
Fax: 249-7393
Email:
Permit Manager: Tony Barganier
Phone: 343-8339
Project: 5th ave mall fire alarm
Review Number: 343156
____________________________________________________________________________________
PERMIT STATUS: Corrections
1) Provide information on the elevators as to the location of the elevator machine room or space and the elevators control room or space to verify these areas are not subject to water discharge. Have the elevator company responsible for the elevators fill out the information sheet provided to enable us to verify full function compliance. ATS will coordinate with the elevator inspectors for a final inspection of the elevators after this scope of work is complete.
2) Provide a complete scope of work that will be performed under this permit and other phased work on the fire alarm.
All submittals should be sent to the permit manager.