Comm T/I to include plum/mech/electric - BWP
**NO CCO OR CO UNTIL CHANGE ORDER FOR CODE STUDY CHANGE AND FLOOR PENATRATION PROTECTION IS SUBMITTED AND APPROVED PER DON CRAFTS 12/30/2014. BWP**
Fire Plan Review
Status: 2nd Submittal-All corrections addressed. Plans Approved by Fire 12/9/14
Comments:
1. A1.0-Hardware sets, #1 Storefront doors-Lock is listed as Thumb turn lock. Thumb turns are prohibited by IBC 1008.,1.9.3, 1008.1.9.5 and by local F.D. Policy. (resolved)
2. This Mall is installing a voice evac fire alarm system. Provide visible/audible alarm devices in this space compatable with the new system being installed. IBC/IFC 907.5.2 & 3. (agreed and resolved)
3. Add exit sign at rear exit visible from front of store. Exit sign shown is flush against wall and not visible from front. (resolved on shown on plans)