Reviewed by: Bolen, Wayne A. Permit #: C13-1177
Phone: 343-8072 Date: 10/23/2014
Fax: 249-7393
Email: BolenWA@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: Alaska Regional Structural Steel Connections Deferred Submittal
Review Number: 342245
____________________________________________________________________________________
PERMIT STATUS
10/23/2014 – Review complete. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
1. EFFECTIVE AREA
Reference page 1 of the calculations. Where rupture strength is checked per AISC 360-05 section D2, Ae is the effective area which must be determined per AISC 360-05 section D3.3 which defines Ae as An*U, where U is per table D3.1. Please provide calculations showing U is 1.0 or revise the rupture strength check to include the actual U factor.