Comm T/I: renovation of the Emergency Department; includes elec, plbg, mech / tb
Reviewed by: Bergstrom, Leigh W. Permit #: C14-1805
Phone: 343-8326 Date: 10/22/2014
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: Alaska Regional Emergency Department
Review Number: 342241
1) STATUS: 8-28-14 Comments to be addressed. 10-22-14 APPROVED.
2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations. RESOLVED 10-22-14.
3) Provide structural, seismic and wind load calculations plus fastening details for RAH-ED1 to include engineers stamp and signature, for structural review on a deferred submittal basis. RESOLVED 10-22-14.
4) M1.02 Fire dampers are required for ducts penetrating Equip Stor #2ED 166 and Stor #2ED 176. (IBC 716.5.2) RESOLVED PER RE-SUBMITTAL RECEIVED 10-20-14.
5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. RESOLVED 10-22-14.