Reviewed by: Crafts, Donald E. Permit #: C14-1704
Phone: 343-8451 Date: 08/27/14, 11/21/14, 11/24/14
Fax: 249-7652
Email: CraftsDE@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierT@muni.org
Project: WEST HIGH SCHOOL - 1700 HILLCREST DR
Review Number: 341888
1. Status: Footing and Foundation Architectural Approval. Please resolve comments for full approval. Please provide complete submittal for full Architectural review. 09/09/14 Status: Architectural Corrections required. Review not complete. 11/24/14
2. The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued. The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.
3. Drawing No. A004, Code Compliance, Applicable Codes; Add the following codes to this section: International Energy Conservation Code (IECC) 2006, and Accessible and Useable Buildings and Facilities (ICC/ANSI A117.1) 2003. 09/09/14 RESOLVED. 11/21/14
4. Drawing No. WA112, The Mechanical Room C260 is shown with one exit. Two exit access doors are required in boiler, incinerator, and furnace rooms where the area is over 500 square feet and any fuel fired equipment exceeds 400,000 British Thermal Units input capacity per IBC Sec. 1015.3. Verify that Mechanical Room C260 meets this code section; identify any boiler equipment located in this room. 11/21/14