Permit Number: C14-1704
Permit Type: Commercial Building Permit - None BldgCombo
Address: 1700 HILLCREST DR Anchorage
Location:
Work Description: 27,000 sq ft add'n & renovation in support of career technology classrooms @ West High School / tb
Status: Closed
Project Name: WEST HIGH SCHOOL
Review Type: Architectural
Result: Correction
Result Date: 11/24/2014 2:48:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Crafts, Donald E.                                                  Permit #: C14-1704

Phone: 343-8451                                                                      Date: 08/27/14, 11/21/14, 11/24/14

Fax: 249-7652

Email: CraftsDE@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierT@muni.org

Project: WEST HIGH SCHOOL - 1700 HILLCREST DR

Review Number: 341888

 

1.  Status: Footing and Foundation Architectural Approval.  Please resolve comments for full approval.  Please provide complete submittal for full Architectural review.  09/09/14  Status: Architectural Corrections required.  Review not complete.  11/24/14

 

2.  The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued.  The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.

 

3.  Drawing No. A004, Code Compliance, Applicable Codes; Add the following codes to this section: International Energy Conservation Code (IECC) 2006, and Accessible and Useable Buildings and Facilities (ICC/ANSI A117.1) 2003.  09/09/14   RESOLVED. 11/21/14

 

4.  Drawing No. WA112,  The Mechanical Room C260 is shown with one exit.  Two exit access doors are required in boiler, incinerator, and furnace rooms where the area is over 500 square feet and any fuel fired equipment exceeds 400,000 British Thermal Units input capacity per IBC Sec. 1015.3.  Verify that Mechanical Room C260 meets this code section; identify any boiler equipment located in this room.  11/21/14