Permit Type: Commercial Building Permit - None BldgAdd
Address: 2500 MINNESOTA DR Anchorage
Location:
Work Description: ADDITION AND RENOVATION IN SUPPORT OF CAREER TECHNOLOGY CLASSROOMS AT ROMIG SCHOOL-GJS
Status: Closed
Project Name: WRCTE ADDITIONS AND RENOVATIONS
Review Type: Mechanical
Result: Correction
Result Date: 10/20/2014 11:17:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C14-1705

Phone: 343-8326                                                                           Date: 10/20/2014

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: Romig Middle School Addition & Renovation 

Review Number: 341882

 

1) STATUS:   8-14-14 Approved for footing, foundation and underground only. Provide 100% drawings. Comments to be addressed.         10-20-14 COMMENTS TO BE ADDRESSED.

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.

 

3) Provide structural, seismic and wind load calculations as applicable, plus fastening details for R-GT-1, R-DC-1 & ROA5 to include engineers stamp and signature, for structural review on a deferred submittal basis.

 

4) RM004            Provide the minimum outside air setting required for ROA5 per IMC Table 403.3.

 

5) 7/MR803         Dryer exhaust duct discharge outlets are required to have backdraft dampers per IMC 504.4.

 

6) 7/MR803         Clarify the reference to IMC 540.

 

7) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.             RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.

 

 

 

 