Fire Plan Review
Initial Review 9/5/14
full package review 10/23/14
Review Status: F&F Approved only. Comments on Architectural
Comments:
1. Submit full package for review. F&F only, approved 9/5/14 C. Hill
2. Classroom R141 I calculate an occuplant load greater than 50 between the two areas. Is this a vocational room/assessory area and if so, provide separation. If calculated as a classroom, a 2nd exit is required, or explain that the kitchen portion will be used only by the same people using the classroom portion.
3. Classroom R141-what type of class will this be? Nevermind, I see the stovetops and ovens.
4. Mechanical Room 300 requires an extinguisher.
5. No extinguishers are shown in the corridor R8000, so extinguishers will be required in classroom R141 andf R147.
6. RA453-Keynote 12-resin panel...Provide smoke and flame spread details.
7. RM004 indicates a dust collector. Show on plans where that will be located. What types of equipment will be dust producing and how many? I see possibly 2 table saws, but 10 connections?
8. Verify there will be no use of heating or other devices using an open flame, or other spark producing equipment in the area where the combustible dust is produced.