Permit Number: C14-1705
Permit Type: Commercial Building Permit - None BldgAdd
Address: 2500 MINNESOTA DR Anchorage
Location:
Work Description: ADDITION AND RENOVATION IN SUPPORT OF CAREER TECHNOLOGY CLASSROOMS AT ROMIG SCHOOL-GJS
Status: Closed
Project Name: WRCTE ADDITIONS AND RENOVATIONS
Review Type: Fire
Result: Correction
Result Date: 10/30/2014 2:31:08 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Fire Plan Review

 

Initial Review 9/5/14

full package review 10/23/14

 

Review Status: F&F Approved only.  Comments on Architectural

 

Comments:

 

1.  Submit full package for review.  F&F only, approved 9/5/14 C. Hill

 

2.  Classroom R141 I calculate an occuplant load greater than 50 between the two areas.  Is this a vocational room/assessory area  and if so, provide  separation. If calculated as a classroom, a 2nd exit is required, or explain that the kitchen portion will be used only by the same people using the classroom portion.

3.  Classroom R141-what type of class will this be?  Nevermind, I see the stovetops and ovens. 

 

4.  Mechanical Room 300 requires an extinguisher.

 

5.  No extinguishers are shown in the corridor R8000, so extinguishers will be required in classroom R141 andf R147.

 

6.  RA453-Keynote 12-resin panel...Provide smoke and flame spread details.

 

7.  RM004 indicates a dust collector.  Show on plans where that will be located.  What types of equipment will be dust producing and how many?  I see possibly 2 table saws, but 10 connections?   

 

8.  Verify there will be no use of heating or other devices using an open flame, or other spark producing equipment in the area where the combustible dust is produced. 

 

 