Reviewed by: Crafts, Donald E. Permit #: C14-1705
Phone: 343-8451 Date: 08/19/14, 11/21/14, 11/25/14
Fax: 249-7652
Email: CraftsDE@muni.org
Permit Manager: Gretchen Stuller
Phone: 343-8320
Email: StullerG@muni.org
Project: WRCTE ADDITIONS AND RENOVATIONS - 2500 MINNESOTA DR
Review Number: 341879
1. Status: Footing and Foundation Architectural Approval. Please resolve comments for full approval. Please provide complete submittal for full Architectural review. 09/09/14 Status: Architectural Corrections required. 11/21/14 (Comments 4 and 7 resolved on 11/25/14 per Fire responses)
2. The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued. The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.
3. Drawing No. A004, Code Compliance, Applicable Codes; Add the following codes to this section: International Energy Conservation Code (IECC) 2006, and Accessible and Useable Buildings and Facilities (ICC/ANSI A117.1) 2003. 09/09/14 RESOLVED. 11/21/14
4. Drawing No. RA111, There appears to be an occupant load greater than 50 (close to 150) between the two areas (east and west ) of Classroom R141. The intended use seems to be for a vocational room/assessory area...confirm? Indicate exiting plan or provide separation. If this area is used/calculated as a classroom, then a 2nd exit is required. Is it possible that the east kitchen area will be used only by the same students that are using the classroom area to the west? 11/21/14 RESOLVED. Per response to Fire comments. 11/25/14
5. Drawing No. RA322, The wall types are stated on these sections; however, thewall type deignators are not indicated that relate to Drawing No. A002 and Drawing No. A003. 11/21/14
6. Drawing No. RA450, The Accessible Lavatory/Sink Height is not indicated on these details. Please verify that Accessible Lavatory Flood Rim Heights shall be 34” maximum above the floor per "Accessible and Useable Buildings and Facilities" (ICC/ANSI A117.1) 2003, section 606.3.
11/21/14
7. Drawing No. RA453, Sheet Keynote No. 12 indicates a resin panel. Where is this used? Provide smoke and flame spread details per .IBC Section 803 (or other applicable section). 11/21/14 RESOLVED. Per response to Fire comments. 11/25/14
8. Drawing No. General, Note that Special Inspection is required for all applications of sprayed fire-resistant materials in accordance with IBC Section 1704.12. Please provide a Special Inspector for this sprayed fire-resistant material application. 11/21/14
9. Drawing No. A580, Detail 1, It is not totally clear where this detail is used; however, verify compliance with the following local ammendment to the IMC:
23.20.306.5 Equipment and appliances on roofs or elevated
structures.
Add exception number 2 to section 306.5 as follows:
2. Where equipment requiring access and appliances are
installed on the roof of a new building, such access shall be
provided by a permanent approved means, interior to the
building, extending from floor level to the equipment and/or
appliances level service space, regardless of the roof height.