Reviewed by: Bolen, Wayne A. Permit #: C14-1850
Phone: 343-8072 Date: 9/17/2014
Fax: 249-7393
Email: BolenWA@muni.org
Permit Manager: Kevin Collins
Phone: 343-8034
Email: ParkerRW@muni.org
Project: H&R Block Sign
Review number: 339493
____________________________________________________________________________________
PERMIT STATUS
9/17/2014 – Review complete. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
1. Screws into aluminum must be austenitic stainless steel or aluminum per the Aluminum Design Manual section 5.4.1. Please clarify the fastening. It may be difficult to find a concrete screw of austenitic stainless steel so it may be better it indicate a different fastener type. It is also acceptable to use galvanize screws with a neoprene grommet or similar separation element.
2. Unless the concrete remains dry and no corrosive additives such as chloride was added to the concrete aluminum connected to the concrete must be protected per the Aluminum Design Manual section 6.7.3