Reviewed by: Bolen, Wayne A. Permit #: C14-1960
Phone: 343-8072 Date: 12/5/2014
Fax: 249-7393
Email: BolenWA@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: Inlet Tower Canopy
Review Number: 341130
____________________________________________________________________________________
PERMIT STATUS
10/13/2014 – Review complete. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
1. Please provide foundation drawings stamped by an Engineer licensed in Alaska as required by the Alaska State Statutes section 08.48.221.
2. Please provide a foundation under the window system that is frost protected per IBC section 1809.5. It must be clarified whether this new enclosed area is heated or not as well as the frost protection requirements are different for heated and unheated structures.
3. Please provide a complete set of window wall drawings showing the construction of the window wall system including connections to the existing structure and connections to the foundation. These connections must be designed to resist the required wind loads. Reference AAC section 23.10.104.8 and IBC section 1605.
4. The wind area at the addition of these elements has been increased. Please provide substantiating data showing the demand capacity ratio of any existing lateral element has not been increased by more than 10% or where it has show that it meets current code requirements. This also applies to the seismic loads. Reference IEBC section 303.4.