Reviewed by: Crafts, Donald E. Permit #: C14-1960
Phone: 343-8451 Date: 10/17/14
Fax: 249-7652
Email: CraftsDE@muni.org
Permit Manager: Robert Parker
Phone: 343-8391
Email: ParkerR@muni.org
Project: Inlet Towers - 1020 W 12TH AVE
Review Number: 341128
1. Status: Architectural Corrections required. 10/17/14
2. The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued. The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.
3. Drawing No. Plan; The construction type of this building is 1A. When existing the canopy is enclosed, the canopy becomes an addition. Additions to this building need to be construction type 1A. 10/17/14