Fire Plan Review
Initial review 9/30/14
Review Status: Comments/corrections
Comments:
1. Add sign over entrance doors "these doors to remain unlocked while space is occupied".
2. IBC 907.2.20 Covered Mall buildings shall have emergency voice evac system. Dimond Center is currently installing the new system, this space shall have system installed prior to stocking.
3. Submit fire alarm and sprinkler plans separately for permitting if needed.
4. AHU/duct detectors shall report into alarm panel.