04/13/2014 – Initial review (328728). Comments issued.
1. EDGE CLEARANCE AT POST-INSTALLED ANCHOR
Refer to Detail Pg. 2 of 8. Please clarify the edge clearance distance for the anchors embedded close to the deck opening.
Reference: IBC Section 1603.1; AMC 23.10.104.8.1
2. ROD COMPRESSION CAPACITY
Refer to Detail Pg 7 of 8. Please clarify the compression capacity of the rod hangers; the details do not provide any information on the maximum unbraced compression length of suspended equipment.
Reference: IBC Section 1603.1; AISC 360 Section E3