Permit Number: C14-1805
Permit Type: Commercial Building Permit - None BldgAlter
Address: 2801 DEBARR RD Anchorage
Location:
Work Description:

Comm T/I: renovation of the Emergency Department; includes elec, plbg, mech / tb


Status: Closed
Project Name: ALASKA REGIONAL EMERGENCY DEPARTMENT
Review Type: Mechanical
Result: Correction
Result Date: 8/28/2014 4:42:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C14-1805

Phone: 343-8326                                                                           Date: 8/28/2014

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: Alaska Regional Emergency Department

Review Number: 338783

 

1) STATUS:   8-28-14 Comments to be addressed.

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.

 

3) Provide structural, seismic and wind load calculations plus fastening details for RAH-ED1 to include engineers stamp and signature, for structural review on a deferred submittal basis.

 

4) M1.02            Fire dampers are required for ducts penetrating Equip Stor #2ED 166 and Stor #2ED 176. (IBC 716.5.2)

 

5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.                                 RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.

 