Comm T/I: renovation of the Emergency Department; includes elec, plbg, mech / tb
Reviewed by: Crafts, Donald E. Permit #: C14-1805
Phone: 343-8451 Date: 09/30/14
Fax: 249-7652
Email: CraftsDE@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierT@muni.org
Project: ALASKA REGIONAL EMERGENCY - 2801 DEBARR RD
Review Number: 338779
1. Status: Architectural Corrections required. 10/07/14
2. The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued. The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.
3. Drawing No. CVR, Plan Review Data; Revise: National Electric Code (NEC) 2008 Edition to National Electric Code (NEC) 2011 Edition. 10/07/14
Note that Special Inspection is required for all applications of sprayed fire-resistant materials in accordance with IBC Section 1704.12. Please provide a Special Inspector for this sprayed fire-resistant material application.
Please resolve all fire comments and copy me on the responses.