Reviewed by: Bolen, Wayne A. Permit #: C13-1821
Phone: 343-8072 Date: 9/12/2014
Fax: 249-7393
Email: BolenWA@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: Alaska Regional Patient Lifts
Review Number: 338753
____________________________________________________________________________________
PERMIT STATUS
9/12/2014 – Review complete. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
1. DEAD LOAD
Please provide the weight of the lifts. ASCE 7-05 Chapter 13 requires elements weighing 20 lbs or more and anchored more than 4' above the floor below to be seismically braced. It may be possible to suspend the equipment per ASCE 7-05 section 13.6.1.
2. PENETRATIONS THROUGH SUSPENDED CEILINGS
Unless rigid bracing is used per comment 1, ASCE 7-05 section 13.5.6.2.2(e) requires a 2 in oversized ring, sleeve or adapter through the ceiling tile to allow for free movement of at least 1 in all horizontal direction. Please verify this is met.
3. STAMPED DRAWINGS
Please provide drawings that have been stamped and signed by an engineer licensed in Alaska as required the Alaska State Statutes section 08.48.221.
4. LIKO SUPPORT
The details reference "Liko support dendant & attachment by others." Please clarify what this is. No details have been provided for this system. Please provide or clarify. Reference AAC section 23.10.104.8.
Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revise drawings.