Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C14-1704
Permit Type: Commercial Building Permit - None BldgCombo
Address: 1700 HILLCREST DR Anchorage
Location:
Work Description: 27,000 sq ft add'n & renovation in support of career technology classrooms @ West High School / tb
Status: Closed
Project Name: WEST HIGH SCHOOL
Review Type: Architectural
Result: Correction
Result Date: 9/9/2014 12:19:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Crafts, Donald E.                                                  Permit #: C14-1704

Phone: 343-8451                                                                        Date: 08/27/14

Fax: 249-7652

Email: CraftsDE@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierT@muni.org

Project: WEST HIGH SCHOOL - 1700 HILLCREST DR

Review Number: 337014

 

1.  Status: Footing and Foundation Architectural Approval.  Please resolve comments for full approval.  Please provide complete submittal for full Architectural review.  09/09/14

 

2.  The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued.  The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.

 

3.  Drawing No. A004, Code Compliance, Applicable Codes; Add the following codes to this section: International Energy Conservation Code (IECC) 2006, and Accessible and Useable Buildings and Facilities (ICC/ANSI A117.1) 2003.  09/09/14

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS