Permit Number: C14-1705
Permit Type: Commercial Building Permit - None BldgAdd
Address: 2500 MINNESOTA DR Anchorage
Location:
Work Description: ADDITION AND RENOVATION IN SUPPORT OF CAREER TECHNOLOGY CLASSROOMS AT ROMIG SCHOOL-GJS
Status: Closed
Project Name: WRCTE ADDITIONS AND RENOVATIONS
Review Type: Electrical
Result: Correction
Result Date: 8/1/2014 10:56:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Electrical Comments

 

Reviewed by: David Abuobaid                                                   Permit #: C14-1705

Phone: 343-8333                                                                        Date: 8/1/2014

Fax:     249-7775

Email:  AbuobaidDH@muni.org

Permit  Manager: Tony Barganier

Phone: 343-8339

Email:  BarganierWA@muni.org

Project: West High/Roming Middle (Fax: 272-7733)                     

___________________________________________________________________________________

 

David,
 
I understand that there was a question as to why we had no electrical plans submitted with the Romig CTE Footing & Foundation plan set (Permit #C14-1705).  The reason is that we didn't anticipate having any major underground conduits in the area of work for Romig.  Any branch panels and other large equipment in that area will be fed overhead from the existing MDP.  While it is true that there may be some branch circuit conduits run under the slab to feed other circuits in the new addition, that becomes contractor means and methods and we have no way of knowing which circuits the contractor will run underslab and which will be run overhead (probably most of them).  That is why we didn't show any branch circuit conduits on the F&F plan.
 
In the Romig Business area, we do have some floor boxes that will have at least one conduit feeding them but as the design develops, those floor box locations are subject to change and it was my understanding that branch circuit conduits like this are not typically shown on a F&F permit set.
 
Please let me know if that is acceptable to you.  Call or email if you have any questions.
 
Thanks,
 
Roger Weese, P.E., RCDD
Principal Electrical Engineer
RSA Engineering, Inc.
P: 907-276-0521
F: 907-276-1751
rweese@rsa-ak.com
 
 

REQUIREMENT OF ELECTRICAL SCOPE OF WORK:
There are no electrical plans provided.

Please provide 100% designed engineered drawing by a registered professional electrical engineer of the State of Alaska. Refer to the attached handout No.E0.1 for Engineering Requirements