Reviewed by: Crafts, Donald E. Permit #: C14-1705
Phone: 343-8451 Date: 08/19/14
Fax: 249-7652
Email: CraftsDE@muni.org
Permit Manager: Gretchen Stuller
Phone: 343-8320
Email: StullerG@muni.org
Project: WRCTE ADDITIONS AND RENOVATIONS - 2500 MINNESOTA DR
Review Number: 337002
1. Status: Footing and Foundation Architectural Approval. Please resolve comments for full approval. Please provide complete submittal for full Architectural review. 09/09/14
2. The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued. The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.
3. Drawing No. A004, Code Compliance, Applicable Codes; Add the following codes to this section: International Energy Conservation Code (IECC) 2006, and Accessible and Useable Buildings and Facilities (ICC/ANSI A117.1) 2003. 09/09/14