Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: M14-1629
Permit Type: Commercial Trade Permit - New Mechanical
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: TENANT IMPROVEMENT, CHANGE OF USE. INCLD PLMB, MECH, ELEC - TC
Status: Closed
Project Name: Child of Bldg App C14-1762
Review Type: Plumbing
Result: Approved
Result Date: 8/4/2014 4:21:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                         Permit #: M14-1629

Phone: 343-8326                                                                         Date: 7/18/2014

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tommy Cornell

Phone: 343-8181

Email: CornellTA@muni.org

Project: Dimond Nails

Review Number: 335753

 

1) STATUS:   7-18-14 Comments to be addressed.

 

2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.

 

3) Pedicure chairs are required to have a nationally recognized third party listed approval as an entire assembly. Please clarify.

 

4) Backflow protection is required on the domestic hot and cold water supplied to the pedicure chairs. (UPC 603) Provide clarification.

 

5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature.                                     RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.

 

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter