Permit Number: C14-1563
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

New Comm T/I to include exterior face lift, plumb, mech, and elect - BWP

CCO ISSUED 4/3/2015-GJS

Status: Closed
Project Name: H & M
Review Type: Plumbing
Result: Approved
Result Date: 7/24/2014 11:28:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W. / Crafts, Donald E.                   Permit #: C14-1563

Phone: 343-8326 / 343-8451                                                          Date: 7/08/2014, 7/24/2014

Fax: 249-7615 / 249-7652

Email: BergstromLW@muni.org / CraftsDE@muni.org

Permit Manager: Bob Parker 

Phone: 343-8391

Email: ParkerRW@muni.org

Project: H & M Retail Store 

Review Number: 336719

 

1) STATUS:   7-8-14 Comments to be addressed.   Status: Full Plumbing Approval.  07/24/14

 

2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.

 

3) M202         The elevator sump pump (SP-1) is required to be placed in a 24” x 24” x 24” sump and if the elevator is hydraulically driven the pumped discharge is to be processed through an oil water separator. (MOA Policy #L.02) Please clarify and co-ordinate with architectural and structural.    RESOLVED.  07/24/14

 

4) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature.                               RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.

 