Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C14-1563
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

New Comm T/I to include exterior face lift, plumb, mech, and elect - BWP

CCO ISSUED 4/3/2015-GJS

Status: Closed
Project Name: H & M
Review Type: Mechanical
Result: Approved
Result Date: 7/24/2014 11:28:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W. / Crafts, Donald E.                   Permit #: C14-1563

Phone: 343-8326 / 343-8451                                                          Date: 7/08/2014, 7/24/2014

Fax: 249-7615 / 249-7652

Email: BergstromLW@muni.org / CraftsDE@muni.org

Permit Manager: Bob Parker 

Phone: 343-8391

Email: ParkerRW@muni.org

Project: H & M Retail Store 

Review Number: 336718

 

1) STATUS:   7-8-14 Comments to be addressed.   Status: Full Mechanical Approval.  07/24/14

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.

 

3) Provide structural, seismic and wind load calculations plus fastening details for RTU-1 thru 5 to include engineers stamp and signature, for structural review on a deferred submittal basis.    DEFERRED SUBMITTAL.  07/24/14

 

4) M201 thru M205            The code study assigned a construction type of "3-B" to the Dimond Center Tower. It was originally built as a Type "1-F.R." ("1-A") and must remain the same. The confusion arose as a result of a meeting several weeks ago where it was agreed that the Dimond Center Mall could be rated as a Type "3B" construction. The Mall and the Tower however, are two separate buildings separated by a two hour fire wall. This being said, the floor ceiling assemblies of the Tower have a 2-Hour rating (Table 601) and any duct penetrations are to be located in a rated shaft (IBC 716.6) with penetrations of the shaft protected with fire/smoke dampers (IBC 716.5.3). If the duct connects not more than two stories the shaft and fire/smoke dampers may be eliminated if the penetration is protected with a fire damper (IBC 716.6.1). Co-ordinate with the architect.    RESOLVED.  This comment is resolved by Redline to the plans.  07/24/14

 

5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.                                 RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.

  

 

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter