Project: Flint Hills rail car expansion
Review Number: 336474
____________________________________________________________________________________
PERMIT STATUS: Corrections
1) Provide a spec sheet on the heads used.
2) Show the mounting of the IR cameras to ensure that damage will not be a problem due to snow and car movement.
3) NFPA 30 section 28.6 is reserved on the required fire protection please explain what NFPA section was used?
Approved 10/15/2014