Permit Number: C14-1635
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: Comm T/I: extend mall corridor through old Forever 21 tenant space; includes elec, plbg, mech / tb
Status: Closed
Project Name: DIMOND CENTER NEW MALL RETAIL CORRIDOR
Review Type: Architectural
Result: Approved
Result Date: 8/7/2014 3:20:06 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Crafts, Donald E.                                                  Permit #: C14-1635

Phone: 343-8451                                                                        Date: 08/06/14

Fax: 249-7652

Email: CraftsDE@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierT@muni.org

Project: DIMOND CENTER NEW MALL RETAIL - 800 E DIMOND BLVD

Review Number: 335537

 

1.  Status: Architectural Corrections required.  08/06/14   Status: Full Architectural Approval.  08/07/14

 

2.  The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued.  The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.

 

3.  Drawing No. A2.1, Partial Floor Plan and Door Schedule; Door PD-11 and Door PD-13 are shown as 20 minute fire-resistance rated.  It appears that Door PD-11 and Door PD-13 are part of an exit passage way and as such should be shown as 60 minute fire-resistance rated.  08/06/14    RESOLVED.  The drawing has been revised by redline to reflect this requirement for both doors.  08/07/14

 

4.  Drawing No. A2.1, Partial Floor Plan and Interior Wall Type Legend; Wall Type C is properly shown as requiring deflection tracking.  Please verify that the provided deflection tracking is required to be UL listed.  08/06/14    RESOLVED.  The drawing has been revised by redline to reflect this requirement.  08/07/14

 

5.  Drawing No. A2.1, Partial Floor Plan; Verify that the south exit from Corridor 111 is an exit enclosure that meets the 60 minute fire-resistance rated requirements.  08/06/14    RESOLVED.  The exit from Corridor 111 is an exit passagway that meets the 60 minute fire-resistance rated requirements.  It was noted that there is no second level at this location and thus the lid does not require a fire-resistance rating.  08/07/14

 

5.  Drawing No. A4.1, Mall Entrance Storefront Elevations and Glass Notes and Schedule; Glass Type B is not shown as requiring safety glazing.  Please verify that Glass Type B is required to be safety glazing.  08/06/14    RESOLVED.  The drawing has been revised by redline to reflect this requirement.  08/07/14