New Comm T/I to include exterior face lift, plumb, mech, and elect - BWP
CCO ISSUED 4/3/2015-GJS
PERMIT INFORMATION
Permit Number: C14-1563
Project Name: H & M Retail Store
Permit Manager: Bob Parker | ph: (907) 343-8391 | parkerrw@muni.org
Plan Review: Mark Panilo | ph: (907) 343-8081 fax: (907) 249-7679 | panilomm@muni.org
Please submit all information through your Permit Manager.
REVIEW STATUS
07/27/2014 – Initial review (334285). Comments issued.
GENERAL
This review is code compliance review based on the requirements of the International Existing Building Code (IEBC), 2009 Edition, and all adopted references thereto, as amended by the Municipality of Anchorage in Anchorage Municipal Code (AMC) Title 23. This review does not permit the violation of the building codes, nor any federal, state, or municipal regulation.
The following comments must be addressed before a permit may be issued. Additional comments may be issued following review of submitted information.
1. DEFERRED SUBMITTALSThe following items have been noted on the plans to be submitted under deferred status:
a. Steel fabricator certification
b. Stair design
c. Exterior cold formed steel stud wall system
d. Curtain wall design
Please provide the following items for code compliance review, or note them on the plans to be submitted under deferred status:
e. Elevator rail support
f. Escalator seismic restraint
All deferred submittals must be sealed by a Professional Engineer licensed in the State of Alaska. Submittals must be reviewed for general conformance by the Registered Design Professional prior to submitting to Building Safety for review. Deferred submittals must be reviewed and approved by Building Safety prior to installation/construction.
Reference: AMC 23.10.104.9
2. SPECIAL INSPECTION PERSONNEL
Please provide a letter from the Owner/Owner's Representative, or Special Inspection Agency stating that the Special Inspection Agency has been retained by the Owner to provide special inspection services for the project as required by IBC Chapter 17.
Reference: AMC 23.15.1704.1.4
3. SPECIAL CONDITIONS FOR ESCALATOR RESTRAINT
Please provide design criteria, including required seismic interstory drift allowance for the escalator design.
Reference: IBC Section 1603.1.8
4. EAST EXTERIOR CANOPY LATERAL SYSTEM
Please provide analysis and design calculations for the lateral system of the east exterior canopy.
Reference: IBC Section 1604.4, 1604.8
5. CANOPY FOUNDATION CONNECTION
Please provide design calculations for the foundation corbels supporting the exterior canopy.