New Comm T/I to include exterior face lift, plumb, mech, and elect - BWP
CCO ISSUED 4/3/2015-GJS
Reviewed by: Bergstrom, Leigh W. Permit #: C14-1563
Phone: 343-8326 Date: 7/08/2014
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Bob Parker
Phone: 343-8391
Email: ParkerRW@muni.org
Project: H & M Retail Store
Review Number: 334284
1) STATUS: 7-8-14 Comments to be addressed.
2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.
3) M202 The elevator sump pump (SP-1) is required to be placed in a 24” x 24” x 24” sump and if the elevator is hydraulically driven the pumped discharge is to be processed through an oil water separator. (MOA Policy #L.02) Please clarify and co-ordinate with architectural and structural.
4) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.