Alt Means & Methods: requesting commercial parking garage fire area threshold for sprinkler system protection to be increased to 6,000 sq ft from 5,000 sq ft / tb
**X14-1572 TO CHANGE SIZE OF BUILDING - CANCELLING THIS ALT/MEANS 6/30/2014.BWP**
Reviewed by: Crafts, Donald E. Permit #: C14-1410; X14-1488
Phone: 343-8451 Date: 6/30/2014, 7/2/2014
Fax: 249-7652
Email: CraftsDE@muni.org
Permit Manager: Tommy Cornell / BWP
Phone: 343-8181
Email: CornellTA@muni.org
Project: Marine Storage Building
Review Number: 333730
1. Status: Architectural Corrections required for this Change Order. 06/30/14 This Change Order has been recinded. It is therefore considered N/A. 07/02/14
2. The following comments (for this change order only) based on the 2009 International Building Code (IBC) must be resolved before a permit is issued. The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.
3. Drawing No. (code study), The building is greater than 5,000 SF and is used for storage of commercial vehicles. Therefore, sprinklers are required for this building per IBC Section 903.2.9, Item 4. 06/30/14