Permit Number: X14-1472
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: CHANGE IN CONSTRUCTION TYPE TO IIIB ETC-GJS
Status: Closed
Project Name: Change Order of Bldg App C14-1031
Review Type: Fire
Result: Approved
Result Date: 6/17/2014 9:41:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Corrections Required 6/17/2014 per fire marshall.  Requesting further documentation to include a formal code study, building layout (general floor plan), and inspections to verify conditions.  (Refer to e-mail sent to architect from fire marshal)

.

Is this an "Alternate Means" rather than a straight "Change Order" since the sprinkler system will not be in strict compliance with the 2009 code for malls.  See concern 3 on attached F.I.R.E. Services letter from Ross Fosberg dated 5/14/2014.

.

Are there any other non-compliance items, no matter how small, that need to be addressed in the request?  If yes please add to the submittal and treat as an "Alternate Means".