Permit Number: C14-1410
Permit Type: Commercial Building Permit - None BldgNew
Address: 2020 TIDEWATER RD Anchorage
Location:
Work Description:

6000 SQFT METAL BLDG, S-2, VB-GJS

PERMIT REASSIGNED TO TOMMY C 8/26/2014-GJS

Status: Closed
Project Name: MARINE STORAGE BUILDING
Review Type: Architectural
Result: Correction
Result Date: 6/17/2014 11:27:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                         Permit #: C14-1410

Phone: 343-8326                                                                         Date: 6/17/2014

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tommy Cornell

Phone: 343-8181

Email: CornellTA@muni.org

Project: Marine Storage Building

Review Number: 331820

 

 

1) STATUS:   6-17-14 Comments to be addressed.

 

2) The following comments based upon the 2009 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.

 

3) G1.2          Plumbing fixtures are required for an S-2 occupancy per IBC Table 2902.1. Clarify within the code study the availability of toilet facilities within 500 feet per IBC 2902.3.2.

 

4) 2/A3.1        Provide pre-insulated wall and roof panel information to include manufacturers literature showing compliance with "all of the requirements of IBC 2603.4.1.4" (highlighted or annotated), "R" values per IECC Table 502.2(1) and vapor retarder per local amendment to IECC 502.5.

 

5) Provide footing, foundation and pavement details to include vapor retarder per local amendment to IECC 502.5 and insulation per IECC Table 502.2(1). 

 

6) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature.

RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.

  

 